Field Test Kit for PCB Screening of Electrical Insulating Fluid - 50 ppm Action Level
On-Site Test Kits for Transformer Oil
U.S. EPA SW-846 Method 9079
Designed to be used in the field, Clor-N-Oil is a fast, accurate method to test electrical insulating fluids for the presence of PCB. Each pocket-sized kit contains everything necessary to perform the test in less than 5 minutes. All premeasured reagents are sealed in glass ampules for safe, fast, consistent and accurate results. Screening transformer oil with Clor-N-Oil can eliminate non-PCB fluids from costly laboratory analysis and allows a greater number of samples to be tested at less cost.
Clor-N-Oil is available for testing transformer oil at four different action levels; 20 ppm, 50 ppm and 500 ppm. To eliminate the possibility of false negatives, Dexsil calibrates all Clor-N-Oil test kits on Aroclor 1242. Aroclor 1242 contains the least amount of chlorine (42% by weight) of the Aroclors found in electrical insulating fluids. By calibrating our test kits using Aroclor 1242, the user obtains the most conservative results. When Clor-N-Oil test kits turn purple, you can be assured your oil sample is below the action level.
|